Maintenance
13.4 Firmware update
3. In the "Functions" folder, select the "Firmware update" group.
For a CPU, you can select whether you want to update the CPU or the display.
4. Click the "Browse" button to select the path to the firmware update files in the "Firmware
update" area.
5. Select the correct firmware file. The table in the firmware update area lists all modules for
which an update is possible with the selected firmware file.
6. Click the "Run update" button. If the module can interpret the selected file, the file is
downloaded to the module. If you need to change the CPU operating state, STEP 7
prompts you to do so with dialogs.
NOTE
Updating PROFINET IO device
The R/H system remains in the RUN-Redundant system state if you update an IO device.
Updating the firmware
The "Run firmware after update" check box is always selected.
Once the files have been successfully loaded, the CPU accepts the firmware and operates with
the new firmware.
Procedure with the SIMATIC memory card
Proceed as follows to perform a firmware update using the SIMATIC memory card:
1. Insert a SIMATIC memory card into the SD card reader of your PG/PC.
2. To store the update file on the SIMATIC memory card, select the SIMATIC memory card
under "Card reader/USB memory" in the project tree.
3. Select the "Card Reader/USB memory > Create firmware update memory card" command
in the "Project" menu.
4. Use a file selection dialog to navigate to the firmware update file. You can then also
decide whether to delete the content of the SIMATIC memory card or add the firmware
update files to the SIMATIC memory card.
5. Insert the SIMATIC memory card with the firmware update files into the CPU.
The firmware update begins shortly after the SIMATIC memory card has been inserted.
The display indicates that the CPU is in STOP and is running a firmware update.
The display shows a results screen after completion of the firmware update.
6. The RUN LED on the CPU lights up in yellow and the MAINT LED flashes yellow.
Remove the SIMATIC memory card after the firmware update is complete.
If you subsequently wish to use the SIMATIC memory card as a program card, leave the
SIMATIC memory card in the CPU. To do so, after completion of the firmware update,
select the "Convert memory card" menu item on the display.
Alternatively, you can also convert the SIMATIC memory card to a program card in STEP 7.
336
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD