Installation; Basics - Siemens SIMATIC S7-1500 System Manual

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Installation

6.1

Basics

Installation site
All modules of the S7‑1500R/H redundant system are unenclosed equipment. You may only
install unenclosed equipment in housings, cabinets or electrical operating rooms indoors. The
housings, cabinets and electrical operating rooms must guarantee protection against electric
shock and spread of fire. The requirements for mechanical strength must also be met. The
housings, cabinets, and electrical operating rooms must not be accessible without a key or
tool. Personnel must be trained or approved for access.
Installation position
The S7‑1500R/H redundant system is designed for use in the following mounting positions:
• Horizontal mounting position up to 60 °C
• Vertical mounting position up to 40 °C
NOTE
If you use the synchronization modules Sync Module 1 GB FO 40 km (6ES7960-1FE00-0AA5)
in the CPUs 1517H-3 PN or 1518HF-4 PN, then the following maximum ambient
temperatures apply:
• Horizontal mounting position up to 55 °C
• Vertical mounting position up to 35 °C
Additional information can be found in the section Mechanical and climatic environmental
conditions.
Mounting rail
You can mount the following components on the mounting rails alongside the S7-1500R/H
CPUs, load current supplies:
• Terminals
• Circuit breakers
• Small contactors
• Similar components
These components can influence the installation dimensions for the cable duct.
Modules can be mounted right to the outer edge of the mounting rail.
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
6
153

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500rSimatic s7-1500h

Table of Contents