Siemens SIMATIC S7-1500 System Manual page 75

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Software restrictions
Table 5-4  Software restrictions
Function
Instructions
Display: "Modules" menu com­
mand
SIMATIC Energy Suite
Firmware update
Hardware detection in STEP 7
(read out configuration)
I-device
IRT
Calibrating analog modules
Configured connections
Motion Control
MRPD
Multiuser Engineering
Online functions
OPC UA
Secure OUC
PROFINET send clock
Shared Device
System power supply
Isochronous mode
Testing with breakpoints
Trace
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
5.2 Restrictions compared to the S7-1500 automation system
Restriction
Restrictions for specific instructions: You can find additional inform­
ation in the section Restrictions (Page 217).
Not supported
Not supported
Firmware update via accessible devices is not supported.
Not supported
The S7-1500R/H redundant system cannot be used as an I-device.
Not supported
You can only calibrate analog modules of an IO device in the RUN-
Solo system state.
1. Switch the CPU with redundancy ID 1 to the STOP operating
state.
2. Establish an online connection with STEP 7 to the analog mod­
ule to be calibrated.
3. Perform the calibration of the analog module with STEP 7. You
can find more information on this topic in the STEP 7 online
help.
4. Then start the CPU with redundancy ID 1.
Connection type not support for communication connection. Only
programmed connections are supported.
Motion Control functions are not supported in the CPUs
Not supported
No support for commissioning mode (commissioning a project
online together) in the RUN-Redundant or SYNCUP system state.
In RUN-Redundant system state, only an online connection to
STEP 7 is possible. In the RUN-Solo or STOP system state, multiple
online connections can be established at the same time.
Not supported
Not supported
The TCON instruction is available but not supported.
1 ms only
Not supported
The following parameter is irrelevant:
"System power supply" > "General" > "Connection to supply voltage
L+/No connection to supply voltage L+"
Isochronous mode is not supported
You can only test with breakpoints in the STARTUP (startup OB) or
RUN-Solo system state.
The storage of measurements on the SIMATIC memory card (meas­
urements in the device) is not supported.
Application planning
75