The redundancy connections in S7-1500R are the PROFINET ring with MRP. The CPUs are
synchronized over the PROFINET ring.
Load current supply (optional)
CPU S7-1515R-2 PN
PROFINET cable (redundancy connections, PROFINET ring)
IO device in the PROFINET ring
Switch
IO device outside the PROFINET ring (separated with a switch)
Figure 4-11  S7-1500R configuration variant
S7-1500H
You connect the CPUs to the Industrial Ethernet over a PROFINET interface or using an
additional switch.
S7-1500H supports the following number of PROFINET devices (switches, S7-1500H CPUs,
S7-1500 CPUs (V2.5 or later), HMI devices, and IO devices such as ET 200MP and ET 200SP):
max. 50 in PROFINET ring
S7-1500H supports the following number of IO devices on the H-CPUs: max. 256 in PROFINET
network (ring, line or combined topology)
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
4.1 What is the S7-1500R/H redundant system?
System overview
37