Siemens SIMATIC S7-1500 System Manual page 44

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

System overview
4.2 Configuration
Component
R/H-CPUs
The CPU runs the user program.
Additional features and functions of the CPU:
PROFINET cable
You connect the CPUs and the IO devices in a PROFINET ring or
PROFINET network using PROFINET cables.
Synchronization mod­
You create 2 redundancy connections between the H-CPUs via
ules (for S7‑1500H)
fiber-optic cables using a total of 4 synchronization modules (2
in each H-CPU).
The following synchronization module versions can be ordered:
Fiber-optic cable (for
They connect the 2 synchronization modules per CPU in pairs via
S7‑1500H)
a fiber-optic cable. The following lengths of fiber-optic cables
can be ordered:
4-pin connection plug
The 4-pin connection plug provides the supply voltage.
for CPU supply voltage
Load current supply
The load current supply (PM) supplies the central modules (CPU)
(PM)
with 24 V DC.
If you are using load current supplies, we recommend the
devices from the SIMATIC series. These devices can be mounted
on the mounting rail.
Various models of load current supply are available:
44
Function
Communication via Industrial Ethernet
Communication via PROFINET IO
Redundant mode
HMI communication
Integrated system diagnostics
Integrated protection functions (access and know-how pro­
tection)
Sync module 1 GB FO 10 m: for fiber-optic cables up to 10 m
in length
Sync module 1 GB FO 10 km: for fiber-optic cables up to
10 km in length
Sync module 1 GB FO 40 km: for fiber-optic cables up to
40 km in length
1 m
2 m
10 m
Up to 40 km (additional information on fiber-optic cables in
longer versions can be found in the Industry Mall
(https://mall.industry.siemens.com).
PM 70 W 120/230 V AC
PM 190 W 120/230 V AC
Diagram
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500rSimatic s7-1500h

Table of Contents