Commissioning
11.4 Operating and system states
The following figure shows the operating state transitions of the primary and backup CPU.
Figure 11-10 Operating state transitions
①
POWER ON → STARTUP, POWER ON → SYNCUP
Transition
Description
System state trans
POWER ON → STARTUP
ition
The CPUs implement pairing after switch-on. The redundant system then
switches to STARTUP if:
•
The mode selector is set to the RUN position,
•
The preceding "POWER OFF" was triggered by an interruption of the power
supply,
•
The hardware configuration and program blocks are consistent,
and
•
The startup type "Warm restart - RUN" is set
or
•
The startup type "Warm restart - Operating mode before POWER OFF" is set
and the system was in RUN-Solo, SYNCUP or RUN-Redundant before
POWER OFF.
The CPU that becomes the primary CPU runs the STARTUP.
The primary CPU switches to the STARTUP operating state.
Operating state
POWER ON → STARTUP
transitions
The CPUs implement pairing after switch-on. The primary CPU then switches
to the STARTUP operating state if:
•
The mode selector is in the RUN position;
•
The preceding "POWER OFF" was triggered by an interruption of the power
supply,
282
Effect
After POWER ON → STAR
TUP, the primary CPU
clears the non-retentive
memory and resets the
contents of non-retentive
data blocks to the initial
values of the load
memory. Retentive
memory and retentive DB
contents are retained.
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD