Hitachi RED670 Commissioning Manual page 115

Hide thumbs Also See for RED670:
Table of Contents

Advertisement

1MRK 505 378-UEN Rev. K
(2 x X1set+X0set)/3
IEC05000369 V5 EN-US
Figure 30:
Table
28
Table 27:
Test point
1
2
3
4
5
6
7
8
9
10
Table continues on next page
Line differential protection RED670
Commissioning manual
X
2
1
11
10
12
9
8
25% of RFPEZx
50% of RFPEZx
alt. 80% of
RFPEZx
RFPEZx (Load
encroachment)
Distance protection characteristic with test points for phase-to-earth
measurements
is used in conjunction with figure 30.
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Reach
Set value
X
X1
set
R
0
X
X1
set
R
R1
set
X
0.8 x X1
set
R
0.8 x R1
+ RFPP/2
set
X
0.5 x X1
set
R
0.5 x R1
+ RFPP/2
set
X
0.85 x RFPP x tan (ArgRLd)
R
0.85 x RFPP
X
RLdFw x tan (ArgLd)
R
RLdFw
X
RLdFw x tan (ArgLd)
R
0
X
–0.2143 x RFPP/2
R
0.8 x RFPP/2
X
–0.4 x RLdFw x tan(ArgDir)
R
0.4 x RLdFw
X
0.5 x X1
set
R
–0.23 x X1
set
© 2017 - 2022 Hitachi Energy. All rights reserved
80%
3
50%
4
5
6
R (Ohm/loop)
7
13
ArgDir
IEC05000369-5-en.vsdx
Comments
ArgRLd = angle for the maximal load transfer
Exact: 0.8 x RFPP/2 (ArgDir)
Exact –0.5 x R1
Section 11
Testing functionality by secondary injection
x tan(ArgNegRes-90)
set
109