Self Supervision Check; Trip Circuit Check; Measurement Of Service Currents - Hitachi RED670 Commissioning Manual

Hide thumbs Also See for RED670:
Table of Contents

Advertisement

1MRK 505 378-UEN Rev. K
inserted or the IED is set to test mode from the local HMI. At the end of the secondary injection test it
should be checked that the event and alarm signalling is correct by activating the events and
performing some selected tests.
13.2.2.5

Self supervision check

Once secondary testing has been completed, it should be checked that no self-supervision signals
are activated continuously or sporadically. Especially check the time synchronization system, GPS or
other, and communication signals, both station communication and remote communication.
13.2.2.6

Trip circuit check

When the protection IED undergoes an operational check, a tripping pulse is normally obtained on
one or more of the output contacts and preferably on the test switch. The healthy circuit is of utmost
importance for the protection operation. If the circuit is not provided with a continuous trip-circuit
supervision, it is possible to check that circuit is really closed when the test-plug handle has been
removed by using a high-ohmic voltmeter and measuring between the plus and the trip output on the
panel. The measurement is then done through the trip coil of the circuit breaker and therefore the
complete trip circuit is checked.
Trip circuit from trip IEDs to circuit breaker is often supervised by trip-circuit supervision. It can then
be checked that a circuit is healthy by opening tripping output terminals in the cubicle. When the
terminal is opened, an alarm shall be achieved on the signal system after a delay of some seconds.
13.2.2.7

Measurement of service currents

After a maintenance test it is recommended to measure the service currents and service voltages
recorded by the protection IED. The service values are checked on the local HMI or in PCM600.
Ensure that the correct values and angles between voltages and currents are recorded. Also check
the direction of directional functions such as Distance and directional overcurrent functions.
For transformer differential protection, the achieved differential current value is dependent on the tap
changer position and can vary between less than 1% up to perhaps 10% of rated current. For line
differential functions, the capacitive charging currents can normally be recorded as a differential
current.
The zero-sequence current to earth-fault protection IEDs should be measured. The current amounts
normally very small but normally it is possible to see if the current circuit is "alive".
The neutral-point voltage to an earth-fault protection IED is checked. The voltage is normally 0.1 to
1V secondary. However, voltage can be considerably higher due to harmonics. Normally a CVT
secondary can have around 2.5 - 3% third-harmonic voltage.
Line differential protection RED670
Commissioning manual
Note that the breaker must be closed.
Please observe that the test system does not provide built-in security during this test.
If the instrument should be set on Amp instead of Volts, the circuit breaker naturally
is tripped, therefore, great care is necessary.
Remember to close the circuit directly after the test and tighten the terminal carefully.
© 2017 - 2022 Hitachi Energy. All rights reserved
Commissioning and maintenance of the fault clearing system
Section 13
SEMOD56528-23 v6
SEMOD56528-26 v5
SEMOD56528-30 v4
259

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents