Section 11
Testing functionality by secondary injection
All functional outputs should reset.
11.
Deactivate the trip signal lockout function, set TripLockout = Off and the automatic lockout
function, set AutoLock = Off.
11.12.1.6

Completing the test

Continue to test another function or end the test by changing the TESTMODE setting to Off. Restore
connections and settings to the original values, if changed for testing purposes.
11.13

Monitoring

11.13.1

Gas medium supervision SSIMG

Prepare the IED for verification of settings as outlined in Section
in this chapter.
Values of logical signals for SSIMG protection are available on the local HMI under Main menu /
Test /Function status /Monitoring /InsulationGas /SSIMG:x , where x = 1, 2,....21.
The Signal Monitoring in PCM600 shows the same signals that are available on the local HMI.
Check that the input logical signal BLOCK is logical zero and that on the local HMI, the logical signals
PRESALM , PRESLO , TEMPALM , TEMPLO , ALARM and LOCKOUT are logical zero.
Using service kit. prepare the IED for verification of settings as outlined in Section
to verify
11.13.1.1

Function revision history

Document
revision
A
B
C
D
E
F
G
H
11.13.1.2
Testing the gas medium supervision for pressure alarm and pressure
lockout conditions
1.
Connect the binary inputs to consider gas pressure and gas density to initiate the alarms.
2.
Activate the binary input SENPRESQ.
3.
Consider the analogue pressure input SENPRES and set SENPRES to a value lower than
PresAlmLimit or activate binary input signal SENPRESALM, check that outputs PRESALM and
ALARM are activated after a set time delay of tPressureAlarm .
4.
Gas pressure lockout input SETPLO can be used to set PRESLO.
236
settings"in this chapter.
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
Binary quality inputs SENPRESQ and SENTEMPQ have been added for pressure and
temperature sensor signals in order to control alarm and lockout signals. Whenever there
is no sensor, the quality of the binary input will be low. If sensor quality is low, then
lockout and alarm signals will get reset.
2.2.5
-
© 2017 - 2022 Hitachi Energy. All rights reserved
1MRK 505 378-UEN Rev. K
GUID-0A83B4D5-51FF-43CB-8DC7-AFCEA2BC7B69 v5
"Preparing the IED to verify settings"
"Preparing the IED
GUID-7F31EFA5-F8D8-4D8D-85DA-3418F70ABE94 v2
GUID-768DAAC8-F89D-4401-B86D-9B26FD7224F6 v5
Line differential protection RED670
Commissioning manual