1MRK 505 378-UEN Rev. K
IEC140000144 V1 EN-US
Figure 16:
Captured synchrophasor data
9.5.2

Verifying the IEEE C37.118/1344 UDP communication

After setting both PMU configuration and the UDP client configuration (As explained in sections
Setting the PMU station communication (PMU
(PMU configuration)
Ethernet communication is set up, click Connect on the PMU Connection Tester tool.
IEC140000145 V1 EN-US
Figure 17:
Now it should be possible to see the streaming synchrophasor data.
Verify the communication by following the same steps as in section
C37.118/1344 TCP
Line differential protection RED670
Commissioning manual
and
Setting the TCP/UDP client
Verifying the UDP communication using PMU Connection Tester
communication.
© 2017 - 2022 Hitachi Energy. All rights reserved
Establishing connection and verifying the IEEE C37.118/1344 communication
Report),
Setting the PMU station communication
communication) and making sure that the
GUID-F0D1117D-3D0F-498F-A00C-242763F8A4E6 v1
IEC140000145-1-en.vsd
Verifying the IEEE
Section 9
77