Huawei UPS5000-E-200K-SM User Manual page 179

50 kva power modules
Hide thumbs Also See for UPS5000-E-200K-SM:
Table of Contents

Advertisement

UPS5000-E-(200 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Figure 4-1 Settings Wizard
Step 4 After you set parameters on the Settings Wizard screen, the system displays the
Bypass mode and No battery alarms, which do not need to be handled. Other
alarms need to be handled.
Issue 17 (2023-07-10)
NO TE
● Set the time and date correctly. Incorrect time and date will cause false fault analysis
during maintenance or repair, affecting the normal operation.
● If you need to use the iManager-M function, perform operations by referring to
(Optional) iManager-M Service
iManager-M.
● After you set network parameters, connect the UPS to the network over a network
cable, which enables you to remotely manage the UPS. If you do not need remote
management, retain the default network parameter settings.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Single UPS Commissioning
Access. Otherwise, retain the default setting of
4.1.3.1
171