UPS5000-E-(200 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Step 3 Connect ground cables, as shown in
Figure 3-99 Grounding
Step 4 Route power cables.
●
Issue 17 (2023-07-10)
NO TE
▪
The quantity of holes in the above figure is for reference only.
▪
If holes are drilled for routing cables, attach grommet strips to the hole edges
to protect cables.
NO TE
●
: Internal equipotential connection
●
: Protection ground
Two power sources
Remove the copper bar between mains and bypass input terminals, as shown
in
Figure
3-100.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Figure
3-99.
3 Installation
144