UPS5000-E-(200 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Item
EMC
9.5 Mains Input Electrical Specifications
Item
Input system
Rated input voltage
Input voltage
Rated frequency
Input frequency
Input PF
THDi
Overvoltage category
Issue 17 (2023-07-10)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Specifications
EN 62040-2
IEC 62040-2
IEC 61000-2-2
IEC 61000-4-2
EN 61000-4-6
EN 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-8
Specifications
Three-phase four-wire + PE. If current is allowed in
the PE wire, input without the N wire is supported.
380 V AC/400 V AC/415 V AC (line voltage)
80–280 V AC (phase voltage)
● At 40°C: The UPS works at full load when the
voltage is 187–280 V AC and is derated to 40%
load when the voltage is 187–80 V AC.
● At 30°C: The UPS works at full load when the
voltage is 176–280 V AC and is derated to 40%
load when the voltage is 176–80 V AC.
50 Hz/60 Hz
40–70 Hz
● > 0.99 (full load)
● > 0.98 (half load)
● THDi ≤ 3% (full linear load)
● THDi ≤ 5% (full non-linear load)
OVC II
9 Technical Specifications
227