Huawei UPS5000-E-200K-SM User Manual page 184

50 kva power modules
Hide thumbs Also See for UPS5000-E-200K-SM:
Table of Contents

Advertisement

UPS5000-E-(200 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Procedure
Step 1 Set the DIP switch.
Figure 4-5 DIP switch
(1) DIP switch
Each ambient T/H sensor has a unique DIP switch address, ranging from 32 to 44.
A DIP switch has six binary toggle switches. The bit on the leftmost is the most
significant bit, and the bit on the rightmost is the least significant bit. Bit 1
indicates ON, and bit 0 indicates OFF.
Table 4-1 DIP switch address mapping
No.
6
5
4
3
2
1
When an ambient T/H sensor is used as a battery temperature sensor, set the DIP
switch to a value in the range of 16 to 28 to monitor the battery temperature.
Issue 17 (2023-07-10)
NO TE
The RS485_R DIP switch is used to enable a build-out resistor so that the ambient T/H
sensor can communicate with the controller. If there are no more than four ambient T/H
sensors on the bus, the RS485_R DIP switch does not need to be set. If there are more than
four, flip the RS485_R DIP switch of the ambient T/H sensor furthest from the UPS to ON.
DIP switch settings on ambient T/H sensors
RS485 Address
32
33
34
1
1
1
0
0
0
0
0
0
0
0
0
0
0
1
0
1
0
DIP switch settings on battery temperature sensors
Copyright © Huawei Digital Power Technologies Co., Ltd.
35
36
37
38
1
1
1
1
0
0
0
0
0
0
0
0
0
1
1
1
1
0
0
1
1
0
1
0
4 Single UPS Commissioning
39
40
41
42
1
1
1
1
0
0
0
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
43
44
1
1
0
0
1
1
0
1
1
0
1
0
176