Huawei UPS5000-E-200K-SM User Manual page 80

50 kva power modules
Hide thumbs Also See for UPS5000-E-200K-SM:
Table of Contents

Advertisement

UPS5000-E-(200 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Port
Descript
ion
PE
Table 3-4
E-300K-SM/SMT.
Table 3-4 Power cable terminal requirements for the 300 kVA cabinet
Port
Descript
ion
Mains
input
Bypass
input
Battery
input
Output
PE
Table 3-5 Recommended upstream input and downstream output circuit breakers
Model
UPS5000-
E-200K-
SM/FM,
UPS5000-
E-300K-
SM/SMT
Issue 17 (2023-07-10)
Connection
Method
Crimped OT
terminals
lists the requirements for power cable terminals of the UPS5000-
Recommende
d Connection
Method
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
UPS Capacity
50 kVA
100 kVA
Copyright © Huawei Digital Power Technologies Co., Ltd.
Bolt
Bolt Hole
Specifica
Diameter
tions
M10
10.5 mm
Bolt
Bolt Hole
Specifica
Diameter
tions
M12
13.5 mm
M12
13.5 mm
M12
13.5 mm
M12
13.5 mm
M12
13.5 mm
Component
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
3 Installation
Bolt Length Torque
30 mm
26 N·m
Bolt Length Torque
45 mm
46 N·m
45 mm
46 N·m
45 mm
46 N·m
45 mm
46 N·m
30 mm
46 N·m
Specifications
160 A/3P
100 A/3P
100 A/3P
250 A/3P
160 A/3P
160 A/3P
a
72