Step 2 Set parameters.
Parameter
WiFi SSID
WiFi password
Enable WiFi
WiFi group sharing
enable
Step 3 Tap Submit.
----End

2.4.5 Setting the System Power Limit Parameter

The default power limit of the unit is 22.3 kW. Power can be adjusted from 15 kW
to 26 kW by limiting the power of the entire system. If power is manually
increased, the power supply may be abnormal, for example, the upstream current
of the unit may exceed the circuit breaker specifications.
The value of System power limit is related to the overall design solution. Do not
change this value unless necessary. If System power limit is set to an incorrect
value, the upstream power supply may be abnormal.
Prerequisites
You need to log in as the admin user.
Issue 02 (2023-08-03)
Description
Set WiFi SSID based on the actual configuration; WiFi
SSID is the name used for the WiFi hotspot over which
a mobile phone can connect to the smart cooling
product.
Enter the WiFi password when you use a mobile phone
to connect to the WiFi. The WiFi has no preset
password. When you enable the WiFi function for the
first time, you need to set a password.
Enables the WiFi function of the smart cooling product.
The default status is Disable.
When a mobile phone is connected to the WiFi of the
smart cooling product, it can access the units in the
same FE cascading network.
CA UTION
Copyright © Huawei Digital Power Technologies Co., Ltd.