FusionCol8000-E140 Modular Indirect Evaporative
Cooling System
Quick Guide (2021, Ireland)
Pipe Anti-freezing
Condensate drainpipes and water refill pipes may freeze and thereby be blocked
or crack in low-temperature areas. Take anti-freezing measures for the pipes.
Wrap the pipes starting from the water refill and drainage ports to the frozen soil
layer with an electric heating belt. Bury the remaining pipes underground (the
temperature at a specific depth underground is always above 0°C).
Figure 1-18
in low-temperature areas.
Figure 1-18 Pipe anti-freezing solution
(1) Water trap
(3) Water refill pipe
(5) Soil
Issue 02 (2023-08-03)
Figure 1-17 Setting sealing putty
(1) Paper protective film
shows the anti-freezing solution for water refill pipes and drainpipes
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Sealing between the
water pipe and sheet metal
(2) Electric heating belt
(4) Drainpipe (connected to the utility
drainpipes)
1 System Installation
(3) Gap between the sheet
metal and the device
21