Huawei FusionCol8000-E140 Quick Manual page 8

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E140 Modular Indirect Evaporative
Cooling System
Quick Guide (2021, Ireland)
● The design and installation of a condensate water trap must meet the
requirements specified in
● The layout and installation of pipes should facilitate the maintenance of the
unit.
Figure 1-1 Water trap installation
Checking Electrical Access for Auxiliaries
The modular indirect evaporative cooling system is an important air handling unit
(AHU). You need to strictly follow the heating, ventilating, and air conditioning
(HVAC) construction requirements. To ensure proper operation of the unit, protect
it against dust, dirt, corrosive gas, and high humidity. Do not use the indoor unit in
open air.
Connection Engineering Precautions
Issue 02 (2023-08-03)
NO TICE
NO TE
● When the device is under negative pressure: H1 = H2 ≥ P/10 + 20 mm.
● P: absolute value of the static pressure at the water pan drain port, measured in Pa.
NO TICE
Air duct installation: A flexible connector should be installed between the unit
and air duct. The air duct should not bear the weight of the unit. Install a
support for an air duct, and ensure that the joint between an air duct and the
unit is not exposed to stress.
Pipe thermal insulation: Take thermal insulation measures for all inlet pipes
and drainpipes of the unit. Reserve sufficient space for maintenance and
operations when installing thermal insulation foam for valves and connectors.
At low temperatures, take thermal insulation measures to prevent water pipes
from freezing.