2.4.2 (Optional) Setting Teamwork Parameters

Prerequisites
The teamwork group number and addresses for the units have been set as follows:
Context
The parameters in this section are for reference only. Set practical parameter
values as required.
Procedure
Step 1 On the home screen, tap
Settings screen.
Figure 2-5 Teamwork Settings
Step 2 Set teamwork parameters.
Set parameters on the master unit (with the smallest address) first. All teamwork
parameters can be set on the master unit. Only Teamwork group num, System
address, Enable teamwork CAN resistor, Teamwork function, Networking
mode, and Teamwork parameter synchronization can be set on slave units.
Other parameters of the slave units will be modified by the master unit
synchronously.
Parameter
Teamwork group num
System address
Issue 02 (2023-08-03)
Teamwork group num: Group the units in same aisle or adjacent areas as one,
that is, assign one teamwork group number for them. At most four teamwork
groups can be assigned (1–4).
System address: The address (configurable range: 1–32) of each unit in the
same group must be unique. The unit with the smallest unit address is the
master unit, which collects, processes, and delivers group data.
Copyright © Huawei Digital Power Technologies Co., Ltd.
> Teamwork Settings to enter the Teamwork
Description
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
Specifies the planned unit address. The addresses of
units in the same teamwork group must be unique.
2 Power-On and Commissioning
45

Advertisement

Table of Contents
loading

Table of Contents