FusionCol8000-E140 Modular Indirect Evaporative
Cooling System
Quick Guide (2021, Ireland)
Menu
Settings > Quick
Settings > T/H Sensor
Issue 02 (2023-08-03)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Parameter
Setting Guide
Balance of
This parameter can be set to Power
water and
saving mode, Normal water-saving
electricity
mode, Extreme water-saving mode,
consumption
or Customized mode. Set this
parameter based on the site
requirements.
NOTE
You are advised to retain the default
value.
DO_1 action
Set this parameter to On or Off
based on the actual scenario.
DO_2 action
Set this parameter to On or Off
based on the actual scenario.
DO_1
Set this parameter as required.
NOTE
You are advised to retain the default
value.
DO_2
Set this parameter as required.
NOTE
You are advised to retain the default
value.
Floor water
Set this parameter to Shutdown,
overflow
Inactivity, Only indoor fan running,
alarm action
Humidifier stopped, or Compressor
& Humidifier stopped based on site
requirements.
NOTE
You are advised to retain the default
value.
Temperature
● When the application scenario is
and humidity
non-aisle containment, you are
control type
advised to choose Return air.
Choose Cold aisle if cold aisle T/H
sensors are configured.
● Hot aisle is not recommended.
Temperature
After Temperature and humidity
setpoint
control type and the temperature
value under this type are set, the
device operates based on the settings.
Humidity
After Temperature and humidity
setpoint
control type and the humidity value
under this type are set, the device
operates based on the settings.
2 Power-On and Commissioning