Huawei FusionCol8000-E140 Quick Manual page 52

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E140 Modular Indirect Evaporative
Cooling System
Quick Guide (2021, Ireland)
Parameter
Networking mode
Enable teamwork CAN
resistor
Teamwork function
Teamwork parameter
synchronization
Number of systems in
this group
Number of running
systems in this group
Issue 02 (2023-08-03)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Specifies the networking mode for teamwork control.
The networking mode selected on the screen must
match the actual networking mode. Otherwise, the
teamwork function is unavailable.
If CAN network is selected, set Enable teamwork
CAN resistor to Yes for the first and last units. If
Enable teamwork CAN resistor is set to No for the
first and last units, the CAN communication quality
will be affected, and even the teamwork CAN
networking will fail.
Yes: The teamwork control CAN resistor is enabled
for the unit.
No: The teamwork control CAN resistor is disabled
for the unit.
Specifies whether to enable the teamwork function.
Set this parameter based on onsite heat load
distribution.
● Disable: A unit operates independently.
● Enable: A unit operates in team with other units.
If Teamwork function and Teamwork parameter
synchronization are both set to Enable, you can
select Set Local or Set Teamwork when setting
parameters.
NOTE
● Set Local: Set parameters for the local unit.
● Set Teamwork: Set parameters for all units in a
teamwork group.
Specifies the total number of units in this group. The
value is an integer ranging from 1 to 32.
Specifies the number of running units in this group.
The value is an integer ranging from 1 to the value
of Number of systems in this group.
2 Power-On and Commissioning
46

Advertisement

Table of Contents
loading

Table of Contents