E K I P T O U C H T R I P U N I T S
12
A DJ U S T I N G T H E S H O R T T I M E P R O T E C T I O N S E T T I N G S
The default setting for Short Time Protection is OFF or ENABLE = OFF
Factory Default Settings
Protection Function
Short Time Protection
S Protection Selective
Short Circuit (51/50TD)
Range Adjustability
Protection Function
Short Time Protection
S Protection Selective Short Circuit
(51/50TD)
1
UL version: t2 Max = 0.4s
Step 13. Press S Protection SelectiveShortCircuit(51/50TD) row
Step 14. Press Enable off row
Frame
Enabled
Trip Enabled
XT5
XT7/XT7M
OFF
ON
Emax 2
Frame
XT5
XT7/XT7M
Emax 2
Function /
Threshold /
Time /
Curve
Pickup
Delay
I2 = 2 x In
t2 = 0.1 seconds
t = k
I2 = 4 x In
t2 = 0.05 seconds
I2 = 2 x In
t2 = 0.1 seconds
Threshold / Pickup Range
0.6 x In to 10 x In; in 0.1 In steps
Thermal
Pre-alarm
Memory
-
-
Time / Delay Range
0.05 - 0.8s in 0.01s steps
1
13
14