Protection settings setup for touch trip units

Advertisement

E K I P T O U C H T R I P U N I T S
22
Step 33. Change the Ground Fault Pickup / Threshold I4 setting to the value in the coordination study.
The setting range is from 0.1 to 1.0 of the breaker's nominal rating (rating plug value) (UL Version: I4 Max =
1200A)
Press the minus icon or the plus icon to change to the value in the coordination study (maintaining the
press will advance the settings faster). Then press Confirm
NOTE: The value is given as both absolute value (Amperes) and in relative value (In) and can be set within the range: 0.1 In to 1.0 In, in steps of 0.001 In
A DJ U S T I N G T H E G R O U N D FA U LT D E L AY O R T I M E T4
Step 34. Press the Time t4 0.40s row
34