ABB Ekip Touch Operating Instructions Manual page 29

Protection settings setup for touch trip units

Advertisement

P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S
29
A DJ U S T I N G T H E L O N G T I M E P I C K U P O R T H R E S H O L D I 1
Step 8. Change the Long Time Pickup / Threshold I1 setting to the value in the coordination study
Pressing Up or Down buttons (8a).
8a
8b
The setting range is from 0.4 to 1.0 of the breaker's nominal rating (rating plug/sensor value)
Press Up or Down buttons (8a) to change to the value in the coordination study. Then Press Enter button
(8b) and this screen will be displayed.
Holding the Up or Down (8a) buttons will advance the settings faster.
NOTE: The value is given as both absolute value (in Amperes) and relative value (In) and can be set within the range: 0.4 In to 1.0In in 0.001 steps
A DJ U S T I N G T H E L O N G T I M E D E L AY O R T I M E T 1
Step 9. Press Down button (9a to select Time T1 setting then press Enter button (9b)
9a
9b