ABB Ekip Touch Operating Instructions Manual page 36

Protection settings setup for touch trip units

Advertisement

E K I P T O U C H T R I P U N I T S
36
Step 24. Change the Instantaneous Pickup / Threshold I3 setting to the value in the coordination study
using the Up and Down buttons (24a) and Press the Enter button (24b).
24a 24b
The setting range is from 1.5 to 15.0 of the breaker's nominal rating (rating plug/sensor value)
Press Up or Down buttons (24a) to change to the value in the coordination study. Then press Enter (24b)
Holding the Up or Down (24a) buttons will advance the settings faster.
Step 25. Press ESC button (25).
25
This completes the settings of the Instantaneous / I Protection function.