P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S
33
A DJ U S T I N G T H E S H O R T T I M E P I C K U P O R T H R E S H O L D I 2
Step 17. Press Down button (17a) to select Threshold I2 and Press Enter button (17b)
17a 17b
Step 18. Change the Short Time Pickup / Threshold I2 setting to the value in the coordination study using
the Up and Down buttons (18a) and Press the Enter button (18b).
18a 18b
The setting range is from 0.6 to 10 of the breaker's nominal rating (rating plug/sensor value)
Press the Up or Down buttons (18a) to change to the value in the coordination study. Then press Enter
button (18b) and this screen will be displayed.
Holding the Up or Down (18a) buttons will advance the settings faster.