E K I P T O U C H T R I P U N I T S
30
Step 10. Change the Long Time Delay / Time T1 to the value in the coordination study using the Up or
Down buttons (10a).
10a 10b
The setting range is from 3 to 144 Seconds
Press the Up or Down buttons (10a) to change to the value in the coordination study. Then press Enter
button (10b) and this screen will be displayed.
Holding the Up or Down (10a) buttons will advance the settings faster.
NOTE: The value is given in seconds and can be set within the range: 3 seconds to 144 seconds, in 1 second steps.
Step 11. Press ESC button (11).
11