Protection settings setup for touch trip units

Advertisement

E K I P T O U C H T R I P U N I T S
16
Step 21. Change the Short Time Delay / Time t2 setting to the value in the coordination study.
The setting range is from 0.05 to 0.8 Seconds (UL versions: t2 Max = 0.4s)
Press the minus icon or the plus icon to change to the value in the coordination study (maintaining the
press will advance the settings faster). Then press Confirm
NOTE: The value is given in seconds and can be set within the range: 0.05 seconds to 0.8 seconds, in 0.01 second steps.
Step 22. Press the left arrow key
22
This completes the settings of the Short Time / S Protection Function.