Protection settings setup for touch trip units

Advertisement

E K I P T O U C H T R I P U N I T S
4 4
A DJ U S T I N G T H E S E CO N D I N S TA N TA N E O U S P I C K U P O R I 3 1
Step 7. Press the I31 Threshold 1.5 In row
7
Step 8. Change the Arc Flash Mitigation / RELT / I31 Threshold setting to the value in the
coordination study.
The setting range is from 1.5 to 15.0 of the breaker's nominal rating (rating plug value)
Press the minus icon or the plus icon to change to the value in the coordination study (maintaining the
press will advance the settings faster). Then press Confirm
NOTE: The value is given as both absolute value (Amperes) and relative value (In) and can be set within the range : 1.5 In to 15.0 In, in 0.1 In steps.