P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S
23
Step 35. Change the Ground Fault Time Delay / Time t4 setting to the value in the coordination study.
The setting range is from Instantaneous to 0.10 to 1.00 Seconds
Press the minus icon or the plus icon to change to the value in the coordination study (maintaining the
press will advance the settings faster). Then press Confirm
NOTE: The value is given in seconds and can be set within the range: 0.10 seconds to 1.00 seconds, in 0.05 second steps.
Step 36. Press the left arrow key
36
This completes the settings of the Ground Fault / G Protection Function.