SERVICE & INSTALLATION MENU
Element
Optional function
Maximum outdoor
temperature to allow
rC
operation mode switch to
heating in auto cooling/
heating with dual set point
Minimum outdoor
temperature to allow
rd
operation mode switch to
cooling in auto cooling/
heating with dual set point
Temperature for the beginning
rE
of heating in setback
Temperature for the beginning
rF
of cooling in setback
S1
Not used
S2
Not used
S3
Not used
55
PMML0565 rev.0 - 09/2021
Individual
Settings
setting
00
Disabled
01
20.0ºC
02
21.0ºC
03
22.0ºC
·
·
·
·
·
·
X
21
40.0ºC
22
0.0ºC
23
1.0ºC
24
2.0ºC
·
·
·
·
·
·
41
19.0ºC
00
Disabled
01
10.0ºC
02
11.0ºC
03
12.0ºC
·
·
·
·
·
·
X
31
40.0ºC
32
-20.0ºC
33
-19.0ºC
34
-18.0ºC
·
·
·
·
·
·
61
9.0ºC
00
15.0ºC
01
16.0ºC
02
17.0ºC
03
18.0ºC
04
19.0ºC
X
05
10.0ºC
06
11.0ºC
07
12.0ºC
08
13.0ºC
09
14.0ºC
00
26.0ºC
01
27.0ºC
02
28.0ºC
03
29.0ºC
04
30.0ºC
X
05
31.0ºC
06
32.0ºC
07
33.0ºC
08
34.0ºC
09
35.0ºC
10
25.0ºC
00
-
-
01
00
-
-
01
00
-
-
01
Setting conditions
Description
If outdoor ambient temperature
is higher than rC, there is no
mode transition to heating
in automatic cooling/heating
operation mode, even if room
temperature reaches the
setpoint to switch operation
mode from cooling to heating.
If outdoor ambient temperature
is lower than rd, there is no
mode transition to cooling
in automatic cooling/heating
operation mode, even if room
temperature reaches the
setpoint to switch operation
mode from heating to cooling.
If room temperature becomes
lower than this setting, indoor
unit operation is resumed in
heating mode by the setback
function.
If room temperature becomes
higher than this setting, indoor
unit operation is resumed in
cooling mode by the setback
function.
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions