Test Run - Hitachi Central Station EX Installation Manual

Air conditioner managing system
Table of Contents

Advertisement

9.6

Test Run

(1) Monitoring and Controlling
NOTICE:
When setting change is made on the monitor window, the contents stay displayed (locked) for a certain
period of time. This display lock expires when the units' states detected on Central Station EX match
the actual operation states of the air conditioners. During this period, operations made on the remote
controller are not affected on the monitor window.
This lock can last for 7 minutes at the longest.
■ Monitoring and Controlling per unit
■ Monitoring and Controlling per group
A12124820A
1.
Set the following configuration in the
monitoring window.
● Display target: All
● Displayed per: Unit:
● Display format: Panel
● Panel size: 1
Refer to the operation manual for
details of the setting procedure.
2.
Control an air conditioner from remote
control and check if the indication on
Central Station EX and the operating
air conditioner match.
3.
Select an air conditioner on Central
Station EX and check if the indication
on Central Station EX and the
operating air conditioner match.
Conduct steps 2 and 3 on each air
conditioner one by one to prevent any
misreads and mistakes.
1.
Set the following configuration in the
monitoring window.
● Display target: All
● Displayed per: Group
● Display format: Panel
● Panel size: 1
Refer to the operation manual for
details of the setting procedure.
2.
Control an air conditioner from remote
control and check if the indication on
Central Station EX and the operating
air conditioner match.
3.
Select an air conditioner on Central
Station EX and check if the indication
on Central Station EX and the
operating air conditioner match.
Conduct steps 2 and 3 on each group
one by one to prevent any misreads
and mistakes.