Hitachi Central Station EX Installation Manual page 51

Air conditioner managing system
Table of Contents

Advertisement

■ Monitoring and Controlling per layout
This step is required only when layout is registered. Refer to "10. Register Layout" (page 50) for detail.
■ Monitoring and Controlling per RC-less air conditioner
If there is an RC-less air conditioner is in the system, follow the instructions below to ensure that the control state of
the RC-less air conditioner on Central Station EX and the actual operation state of the air conditioner match.
A12124820A
1.
Set the following configuration in the
monitoring window.
● Display target: Each layout
● Display format: Layout
2.
Control an air conditioner from the remote
control and check if the indication on
Central Station EX and the operating air
conditioner match.
3.
Select an air conditioner on Central
Station EX and check if the indication on
Central Station EX and the operating air
conditioner match.
Conduct steps 2 and 3 on each layout
one by one to prevent any misreads and
mistakes.
1.
Set the following configuration in the
schedule window.
● Season: Regular season - day of the
week
● Setting target: Group in which RC-less
air conditioner is registered.
* Block, Area and All can also be set up.
2.
Set the following operation pattern to
start in 5 minutes.
Operation
Run/Stop
Temp.
mode
Run
Fan
28°C
3.
At the scheduled time (5 minutes after
step 2), check if the operation pattern
dispalyed in Central Station EX, the
operation pattern from step 2, and
the actual operation state of the air
conditioner all match.
4.
Delete the schedule for the time set in
step 2.
Fan
Louver
speed
Low
1st step
49