Mounting And Installation; Regulations; Heat Pump Controller Rvs; Engineering - Siemens RVS41.813 User Manual

Avs75, avs37, qaa75, qaa78, qaa55 series heat pump controller
Table of Contents

Advertisement

Electrical installation

Engineering

Mounting location

Mounting method

14/258
Siemens Switzerland Ltd
HVAC Products
3

Mounting and installation

3.1

Regulations

• Prior to installing the units, power must be turned off
• The connections for mains and low-voltage are separated
• For wiring, the requirements of safety class II must be satisfied.
• One and the same sensor cannot be connected to several inputs
Sensor and power cables must not be run in the same cable duct
3.2

Heat pump controller RVS..

• Air circulation around the controller must be ensured, allowing the unit to emit the
heat produced by it.
A clearance of at least 10 mm must be provided for the unit's cooling slots at the top
and bottom of the housing.
That space should not be accessible and no objects should be placed there. If the
controller is enclosed in another (insulating) casing, a clearance of up to 100 mm
must be observed around the cooling slots
• The controller is designed conforming to the directives for safety class II devices
mounted in compliance with these regulations
• Power to the controller may only be supplied when completely fitted. If this is not
observed, there is a risk of electric shock hazard near the terminals and through the
cooling slots
• The controller must not be exposed to dripping water
• Permissible ambient temperature when mounted and when ready to
operate: 0...50 °C
• Power cables must be clearly separated from low-voltage cables (sensors) observing
a distance of at least 100 mm
• Heat pump
• Control panel
• Housing for wall mounting
Screwed
User manual RVS61.843, RVS41.813
3 Mounting and installation
On DIN rail
A2
A1
B2
B1
A: Mounting
/
B: Removal
Note:
To mount the controller on a DIN rail, a mounting
clip is required!
2359Z11
CE1U2355en_02
28. September 2009