Mixing Valve Control; Floor Curing Function - Siemens RVS41.813 User Manual

Avs75, avs37, qaa75, qaa78, qaa55 series heat pump controller
Table of Contents

Advertisement

Mixing valve control

Mixing valve boost
Actuator:type
Switching differential
2-pos
Actuator running time

Floor curing function

Siemens Switzerland Ltd
HVAC Products
Important:
The function may only be activated in plants with buffer or combi storage tanks. In the
case of plants without storage tank, there is a risk of a compressor being in operation
without having a consumer pump running.
Line no.
HC1
HC2
830
1130
832
1132
833
1133
834
1134
The controller adds the mixing valve boost set here to the current flow temperature
setpoint and uses the value as the temperature setpoint for heat generation.
2-position
The controller drives the actuator with only one relay output. When the output delivers a
signal, the valve opens. When there is no signal, the valve closes automatically.
3-position
The controller drives the actuator with 2 relay outputs. One of the outputs is used for
opening the valve, the other for closing the valve.
For the 2-position actuator, the "2-position switching differential" must also be adapted.
The switching differential has no impact on 3-position actuators.
For the 3-position actuator, the running time of the mixing valve actuator can be
adjusted. The actuator running time has no impact on 2-position actuators.
The floor curing function serves for controlled drying of the floor. It controls the flow
temperature according to a temperature profile. Drying of the floor is ensured via the
floor heating system by the mixing or pump heating circuit.
• Observe the relevant standards and regulations of the company supplying the floor!
• Proper functioning is ensured only when the plant is correctly installed (hydraulic
system, electrical installation, settings)!
If not observed, the floor might get damaged!
• The function can be aborted by choosing Off .
• Maximum limitation of the flow temperature remains active
User manual RVS61.843, RVS41.813
6 The settings in detail
Operating line
Mixing valve boost
Actuator:type
2-position ¦ 3-position
Switching differential
2-pos
Actuator running time
93/258