Room temperature limitation

Boost heating

90/258
Siemens Switzerland Ltd
HVAC Products
Line no.
HC1
HC2
HC3P
760
1060 1360
The "Room temperature limitation" function enables the heating circuit pump to be
deactivated should the room temperature exceed the current room temperature
setpoint by more than the adjusted differential.
The heating circuit pump will be activated again as soon as the room temperature
returns to a level below the current room temperature setpoint.
During the time the "Room temperature limitation" function is active, no heat request is
sent to the heat source.
Room temperature limitation does not work in the case of pure weather compensation.
°C
ON
P
OFF
Line no.
HC1
HC2
HC3P
770
1070 1370
Boost heating is used to reach the new setpoint more quickly when switching from the
Reduced setpoint to the Comfort setpoint, thus reducing the heating up time. During
boost heating, the room temperature setpoint is raised by the value set here.
A higher setting leads to shorter heating up times, a lower setting to longer heating up
times.
Boost heating is possible with or without room temperature sensor.
°C
TR
w
20
15
TRw
Room temperature setpoint
TRx
Actual value of the room temperature
DTRSA Increase of the room temperature setpoint
User manual RVS61.843, RVS41.813
6 The settings in detail
Operating line
Room temperature limitation
TRx
TRx
temperature
TRw+SDR
TRw
SDR
TRw
P
T
t
Operating line
Boost heating
DTRSA
TR
x
Actual value of the room
The room temperature setpoint
Room's switching differential
Pump
Time
t
CE1U2355en_02
28. September 2009