Siemens RVS41.813 User Manual page 185

Avs75, avs37, qaa75, qaa78, qaa55 series heat pump controller
Table of Contents

Advertisement

Siemens Switzerland Ltd
HVAC Products
U2
Voltage value 2
F2
Function value 2
If the input signal drops below the limit value of 0.15 V, the heat request is invalid and
therefore inactive.
• Example of pressure measurement 10 V
P [bar]
4bar
F
=0
1
0
U
=0.5V
1
P
Pressure value
Hx
Voltage value at Hx
U1
Voltage value 1
F1
Function value 1
U2
Voltage value 2
F2
Function value 2
If the measured value lies below 0.15 V, it is regarded invalid.
• Example of relative room humidity 10 V
rF [%]
F
=100
2
F
=0
1
U1=0V
0.15V
rF
Relative humidity
Hx
Voltage value at Hx
U1
Voltage value 1
F1
Function value 1
U2
Voltage value 2
F2
Function value 2
If the measured value lies below 0.15 V, it is regarded invalid.
User manual RVS61.843, RVS41.813
6 The settings in detail
F2=4
Hx [V]
U
=3.5V
2
U
=10V
2
Hx [V]
185/258
CE1U2355en_02
28. September 2009