Configuration

Setpoints

Only RVS61..

Speed-controlled pump

Only RVS61..
Pump speed min

Mixing valve control

Only RVS61..
Actuator running time

Procedure

168/258
Siemens Switzerland Ltd
HVAC Products
flow, pump Q34 stops.
When using the speed-controlled pump without mixing valve (left), pump Q34 must be
configured to multifunctional output QX4mod. Sensor B38 must be assigned to a
multifunctional input Bx.
In that case, flow switch (FS) is automatically assigned to digital input H1.
If, in place of modulating pump Q34, a pump with fixed speed (on / off) is used,
parameters 5530 (Pump speed min) and 5531 OEM (Pump speed max) must be set to
100%.
When using a mixing valve and a pump with fixed speed (right), parameter 6014
(Function mixing group 1) must be configured to "Instantaneous DHW heater". In that
case, the outputs used with the mixing heating circuit are assigned according to the
table on page 172 (parameter 6014).
In place of the mixing group in the controller, this function can also be assigned to an
extension module. In that case, parameter 6021 or 6022 must be configured to function
"Instantaneous DHW heater" and the assignment table on page 172 applies
(parameters 6020 and 6021).
Line no.
Operating line
5406
Min setp diff to tank temp
The maximum DHW temperature setpoint controlled is the current storage tank
temperature minus the setpoint differential that can be adjusted here.
Line no.
Operating line
5530
Pump speed min
The minimum speed of the pump for instantaneous DHW heater can be defined. It is
thus possible to negate the lowest pump speeds, which cannot be properly controlled.
Line no.
Operating line
5544
Actuator running time
Setting the running time of the actuator used with the mixing valve.

6.20 Configuration

First, make use of the presetting choices and enter the plant diagram that comes
closest to the plant in question. Then, modify manually the individual partial diagrams to
match them to the actual requirements.
After that, select the extra functions and make the fine-tuning via the operating lines of
the individual parameters.