Raising The Reduced Setpoint; Overtemp Prot Pump Heating Circuit - Siemens RVS41.813 User Manual

Avs75, avs37, qaa75, qaa78, qaa55 series heat pump controller
Table of Contents

Advertisement

Raising the Reduced setpoint

Overtemp prot pump heating circuit

92/258
Siemens Switzerland Ltd
HVAC Products
Optimum start / stop control is possible with or without room temperature sensor.
0
Xein
TRx
TRw
Xein
Switch-on time shifted forward in time
Xaus
Switch-off time shifted forward in time
ZSP
Time program
TRx
Actual room temperature
TRw
Room temperature setpoint
Line no.
HC1
HC2
HCP
800
1100
1400
801
1101
1401
The function is used primarily in connection with heating systems with only little spare
capacity (e.g. low-energy houses). In such cases, the heating up time at low outside
temperatures would be too long. When the Reduced setpoint is raised, the rooms are
prevented from cooling down excessively, thus shortening the heating up time when
changing to the nominal setpoint.
TR
TRwA1
TRK
TRR
-15
Line no.
HC1
HC2
HCP
820
1120
1420
In the case of heating plants with pump heating circuits, the flow temperature of the
heating circuit can be higher than the flow temperature called for by the heating curve,
the reason being higher requests from other heat consumers (mixing heating circuit,
DHW charging, external heat demand), or a parameterized minimum heat source
temperature. As a result of this too high flow temperature, the pump heating circuit
would assume excessive temperatures.
Function "Overtemperature protection for pump circuits" ensures that the energy supply
for pump heating circuits corresponds to the demand from the heating curve by
activating / deactivating the pump.
User manual RVS61.843, RVS41.813
6 The settings in detail
ZSP
Operating line
Reduced setpoint increase start
Reduced setpoint increase end
TRwA1
TRwA2
TRwA2
TRK
TRR
TAgem
-5
TAgem
Operating line
Overtemp prot pump heating circuit
Xaus
1/4 °C
Reduced setpoint increase start
Reduced setpoint increase end
Comfort cooling setpoint
Reduced room temperature setpoint
Composite outside temperature
CE1U2355en_02
28. September 2009
24