Setpoints And Actual Values - Siemens RVS41.813 User Manual

Avs75, avs37, qaa75, qaa78, qaa55 series heat pump controller
Table of Contents

Advertisement

Setpoints and actual values

Remaining times
Remain limit source temp
min
Compressors
Compressor sequence
218/258
Siemens Switzerland Ltd
HVAC Products
This rule applies to relays defined as NO contacts. When defined as NC contacts, the
action is reversed.
Line no.
Operating line
8410
Return temp HP
8411
Setpoint HP
8412
Flow temp HP
8413
Compressor modulation
8415
Hot-gas temp 1
8416
Hot-gas temp max
8417
Hot-gas temp 2
8420
Refrigerant temperature liquid
8425
Temp diff condenser
8426
Temp diff evaporator
8427
Source inlet temp
8428
Source inlet temp min
8429
Source outlet temp
8430
Source outlet temp min
These operating lines are used to query the different setpoints and actual values of the
heat pump.
Line no.
Operating line
8440
Remain stage 1 off time min
8441
Remain stage 2 off time min
8442
Remain stage 1 on time min
8443
Remain stage 2 on time min
If the "Min off time" or "Min on time" of stage 1 or 2 is active, these operating lines show
the remaining off time / on time.
Only on completion of the off time is - - - displayed, and theheat pump can be released
again.
Line no.
Operating line
8444
Remain limit source temp min
If the source temperature (B91) is too low, pumps and compressor are locked for the
period of time "Time limit source temp min" (2822). This operating line shows the
remaining period of time for pumps and compressor to be released again.
Line no.
Operating line
8446
Compressor sequence
1 – 2
2 – 1
Shows the current compressor sequence, that is, the order in which the compressors
are put into operation:
1 – 2
First, compressor 1 is put into operation, then compressor 2.
2 – 1
First, compressor 2 is put into operation, then compressor 1.
User manual RVS61.843, RVS41.813
6 The settings in detail
CE1U2355en_02
28. September 2009