Electric immersion heaters in the cascade

Siemens Switzerland Ltd
HVAC Products
On completion of the number of hours set, the heat source sequence in the cascade
changes. It is always the heat source with the next higher device address that takes on
the role of lead heat source.
st
1
changeover 2
P [kW]
K 4
K 1
K 4
K 3
K 2
K 3
K 1
K 2
100
t
= total number of operating hours of all lead heat sources
[kW]
Auto source seq exclusion
connection with the activated source sequence (3540).
With source sequence exclusion, the first and / or the last heat source can be
exempted from automatic changeover.
None
The order of switching on the heat sources changes when the number of hours set is
reached (3540).
First
The first heat source in the addressing scheme always remains the lead heat source.
With the other heat sources, the order of switching on changes when the set number of
hours is reached (3540).
Last
The last heat source in the addressing scheme always remains the last. The other heat
sources change when the set number of hours is reached (3540).
First and last
The first heat source in the addressing scheme always remains the lead heat source.
The last heat source in the addressing scheme always remains the last. The heat
sources in between change when the set number of hours is reached (3540).
@ @
Many heat pumps are equipped with an electric immersion heater (K25) in the flow
(directly after the condenser). The electric immersion heaters can be of the 2- or 3-
stage type (K25 and K26).
If all compressor stages of the cascade are released, the electric immersion heater of
the heat pump with first priority is released. Electric immersion heaters are released
according to the same criteria as heat pumps (release and reset integral). The heat
pump reports to the source master when all stages of the electric immersion heater are
released, or when no electric immersion heater is available.
User manual RVS61.843, RVS41.813
6 The settings in detail
nd
rd
changeover 3
changeover 4
K 2
K 3
K 1
K 2
K 4
K 1
K 3
K 4
200
300
400
Setting of the source sequence exclusion is only used in
th
changeover
Slave source
Lead source
t [h]
=
total output of cascade
CE1U2355en_02
28. September 2009
149/258