Siemens OZS164 SERIES WEB SERVER Commissioning Instructions page 31

Table of Contents

Advertisement

Siemens
Building Technologies
Data point
M essage repetition
Default val.:
3
Setting val:
None, 1, 2, 3,
Unlimited
T ime to next message
Default val.:
0
Setting val:
0... 840 min
(Resolution 1 min)
Web server
Commissioning
Explanation, example
For SMS recipient type:
None means that there is one attempt at
sending the message.
Setting values (n = 1, 2, 3) mean that there
are n+1 attempts at sending messages.
Note
: Setting Unlimited may result in high
p
hone bills.
For SMS recipient type:
Waiting time to next message.