Default State; Update Software - Siemens OZS164 SERIES WEB SERVER Commissioning Instructions

Table of Contents

Advertisement

Restore default state
Notes
System data update
Note
Logo update
Note
46 / 108
Siemens
Building Technologies
2.10

Default state

The web server can be reset to factory default settings. This is probably a good
idea when using the web server for another plant.
Procedure:
1.
Simultaneously press buttons Remote
than 6 seconds.
LED On
turns off. The web server restarts.
2.
Wait until the web server is operational (LED On
When restoring default state:
• All settings are reset to default (also applies to LPB/BSB device address and
Ethernet IP address).
• The device list is deleted.
• Uploaded files are deleted.
• Unsent messages are deleted.
• History data is not deleted (must be deleted manually; see Section 2.8).
2.11

Update software

The web server supports a number of bus devices and differentiates them via
device descriptions. A text catalog with various languages contains all web server
texts and device descriptions. The system data can be updated on site to add
device descriptions for new devices or new languages retroactively.
See Section 3.4 for information on uploading system definitions.
The logos can be customized.
See Section 3.4 for information on uploading logos.
Web server
Commissioning
(6) and Service
(7) for more
is green).
CE1C5711en
25.08.2010