Functional check

Connections must be tested if all settings were made to the web server as well as
to system devices.
A PC on the local network is used to test operations via LAN. The login dialog box
must appear after entering the local IP address for the web server (see Section
2.2.2).
We recommend using mobile participants with Internet access (Smartphone,
mobile phone) to test operation over the Internet. The login dialog box must appear
after entering the public IP address or plant domain (see Section 3).
A text message with plant status is received after a text message (possibly with
p
assword) is sent to the plant's phone number (see Section
1. Create text message:
– Password required: *<Password> #
– No password required: #
2. Send message plant phone number.
Do the test if the web server is to send a message or system report via e-mail or
SMS for a fault.
The test is also carried out if message suppression is switched on.
Path: Home > 0.5 OZS164... > Settings > Message receiver
Data point
T est message receiver
Default val.:
---
Setting val:
Message receiver 1..4
S ystem report sent
Display values: ---, Yes, No
M essage inhibition
Display values: Yes, no
Web server
Commissioning
Explanation, example
Select a message recipient to test the
connection to it.
The display after a few seconds from "
Yes:
Message sent successfully.
N
o:
Message recipient not reached.
Shows the message suppression switch
s
etting (8) (see Section
4).
" to:
---
1.2).
CE1C5711en
25.08.2010
43 / 108