Siemens OZS164 SERIES WEB SERVER Commissioning Instructions page 32

Table of Contents

Advertisement

System report
Note
32 / 108
Siemens
Building Technologies
Path: Home > 0.5 OZS164... > Settings > System report
Enter these settings if you want the web server to send e-mail messages or SMS
(OZS164.23 only) on a regular basis.
Data point
S ignal time
Default val.:
06:00 hh:mm
Setting val:
00:00...23:59
(Resolution 00:01)
M essage cycle
Default val.:
1 d
(day)
Setting val:
0...255 d
(Resolution: 1 d)
P riority
Default val.:
Urgent
Setting val:
Urgent /
Not urgent
N ext report
Default val.:
0 d
(day)
Setting val:
0...255 d
(Resolution: 1 d)
Web server
Commissioning
Explanation, example
The setting value corresponds to the time of
day when a system report is sent (time can be
defined).
The setting value corresponds to the interval
(in days) at which a system report is sent.
The first system report is delivered after
completion of the first message cycle and then
as per the message cycle.
The system report is disabled when the
m
essage cycle =0.
Filter when sending the system reports.
The setting Urgent sends the system report to
all active message recipients. The setting Not
urgent exempts all message recipients
s
ubscribing to "Only urgent ones".
Waiting time to next system report.
CE1C5711en
25.08.2010