Technical Data; Web Browser / Os; Web Server - Siemens OZS164 SERIES WEB SERVER Commissioning Instructions

Table of Contents

Advertisement

Web browser / OS

Number of users
Power supply unit for web
server OZS164...
Web server OZS164...
Functional data
Connection terminals
PC interface
LPB/BSB bus
Ethernet
Digital inputs
94 / 108
Siemens
Building Technologies
6.4

Technical data

6.4.1
Web browser / OS
PC/Laptop (1024 x 786)
iPhone (480 x 320)
Any number of web browsers can be used simultaneously. The max. data traffic on
the line is divided up among the web browsers. As a result, operation slows down
depending on the number of simultaneous users.
6.4.2

Web server

Operating voltage
Rated voltage
Frequency
Power consumption OZS164 (incl. power supply unit)
Protection class
Output voltage
Supply line fusing
Cable length (distance 230 VAC plug to web server)
Operating voltage
Power consumption
Clock reserve
Device list
Screw terminals for
1 solid wire per terminal
1 stranded wire per terminal.
Interface
Standard
Device class
Baud rate
Connection cable for operator station
Cable length
Cable type for connection to PC/laptop
Cable type for connection to OZS164
Interface type
2-wire bus
Bus load
Permissible line length and cable types
Interface type
Bit rate
Protocol
Identification
Connection
Cable type
Cable length
Interface type
Voltage at open contact
Current at closed contact
Web server
Appendix
Internet Explorer V6.0 or higher
Firefox V3.0 or higher
Safari (specific to end device)
AC 100 - 240 V
10 %
±
AC 100 - 240 V
50 / 60 Hz
3 VA typical
II
SELV 24 VDC
Max. 16 A
Max. 1.6 m.
SELV 24 VDC
5 %, 625 mA max.
±
2 W typical
Min. 72 h
1 Bus device
2
0.25...1.5 mm
2
0.25...1.0 mm
USB V2.0
RNDIS
Max. 12 Mbps (full speed)
Max. 3 m
USB type A
USB type Mini-B
2-wire connection
DB/CL+, MB/CL– (non-exchangeable)
E 0.6
See:
- Albatros2 System manual P2359
- Local Process Bus System
engineering basic documentation
P2370
100BaseTX, IEEE 802.3 compatible
100 Mbps
TCP / IP
Auto MDI-X
RJ45 plug (screened)
Standard Cat-5, UTP or STP
Max. 100 m
Protective low voltage for potential-free
low voltage-capable contacts
DC (16...19) V
DC (4...6) mA
CE1C5711en
25.08.2010

Hide quick links: