Final Steps; Check Faults; Final Steps On Web Server - Siemens OZS164 SERIES WEB SERVER Commissioning Instructions

Table of Contents

Advertisement

Fault indicator
Note
No fault
Fault
Final tasks
Note
Siemens
Building Technologies
2.9

Final steps

2.9.1

Check faults

The fault indicator displays the plant state.
No faults may be pending after commissioning. Additional information on faults is
available in Section 3.3.
The fault indicator remains green as long as no fault is pending.
The fault indicator changes to red for faults.
The most severe plant faults are displayed:
• Device name
• Fault text
2.9.2

Final steps on web server

The final function checks are conducted on the web server, the cover is mounted
and the LEDs checked.
On display and operating elements, see Section 1.2.
Procedure:
1.
Unplug USB cable.
2.
Switch off message suppression:
– Remove the cover.
– Message suppression switch (8) must be on "Off"
3.
OZS164.23 only: The SIM card is inserted.
4.
Mount terminal cover.
5.
Press Remote
– The web server sends a system report to the defined message recipients.
– Fault LED
(4) displays (flashing) error in establishing communications.
6.
LED On
must be steady green.
7.
Fault LED
must be dark.
Web server
Commissioning
(6) button for more than 6 seconds.
.
45 / 108
CE1C5711en
25.08.2010

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents