(3) SQL failure log of DB Connection Service
Error code
0x20600001
0x20600002
0x20600020
0x20600021
0x20600022
0x20600023
0x20600025
0x2060002B
8 - 18
8.2 Error Code List
Error description and cause
Failed in SQL execution due to insufficient memory.
Failed in SQL execution due to insufficient resources.
DB Connection Service does not support the SQL
instruction to be executed.
Failed in preparation before SQL execution.
Failed to obtain the number of fields in the record that is to
be obtained by the SQL execution.
Failed in SQL execution.
No record was updated or inserted by the SQL execution.
(Data source name: *** Transmitting Commit Success
Response Failed. ***)
Failed to transmit the COMMIT success response.
Corrective action
• Terminate any unnecessary applications.
• Add more memory to the personal computer.
• Check the source IP address setting.
• Confirm the version of the option OS (MES Interface).
• Correctly set a database type for [DB server setting], a
table name in the job for the communication action
setting, or the resource data send action setting in
[MES Interface].
6.6 Server Service Settings
• Correctly set a database type for [DB server setting], a
table name, field names, Select/Update conditions, and
types of the data to be stored in the fields in the job for
the communication action setting or the resource data
send action setting in [MES Interface].
6.6 Server Service Settings
• In [MES interface setting], set update conditions
correctly for the Communication action setting of the
Job settings.
6.8.1 Setting items in Communication action
• Check if the database has been filled with registered
data.
• Check if it is connected to the network.
• Check if the gateway and/or hub is operating.
• Check if the power of the GOT has not been turned off.