ABB SM3000 User Manual page 95

Multipoint videographic recorder/paperless recorder
Hide thumbs Also See for SM3000:
Table of Contents

Advertisement

...4.6.5 Totalizer Configuration
Analog Input Sources only – see Section 4.6.1
Analog Input Sources only – see Section 4.6.1
Input Signal
3
3
m
/sec
m
/hr
150
0.04167
0.0208
75
Area = total
volume of flow
0
t
1hr
The totalizer pulse rate is
proportional to the input signal.
At this point it is
0.0208 pulses per second
OR
Digital Input Sources only – see Section 4.6.1
Input Signal
On
Off
Units
0
1hr
Totalizer Value
Units
t
0
1minute
1minute
Totalizer Value
Set the required totalizer count rate.
The count rate is determined by the maximum number of
engineering units (or pulses) per second and the smallest
totalizer increment:
engineering full scale value (rate)
engineering units (in seconds)
– to totalize a flow with a maximum rate of
Example
2500 litres/minute (= 2.5m
calculation is as follows:
150 m
3600 seconds
The resulting value must be within the range 0.00001 to
99.99999. The totalizer increment is determined by the
number of decimal places in the 'Predetermined count' value
– see page 92.
Set the required totalizer cut off value.
The totalizer cut off value is the lowest input value (in
engineering units) at which the totalizer is to stop counting.
2000
1000
t
Set the required totalizer count rate.
A digital totalizer pulse can be scaled to represent a value of
between 0.00001 and 1000.00000. The totalizer is then
incremented by this amount each time there is an off/on
transition.
500
400
– a count of 5 digital pulses with 'Count rate' set to
Example
300
100 increments the totalizer from 0 to 500 in 100 unit steps.
200
100
t
4 CONFIGURATION...
3
/minute) to the nearest 0.1m
3
/hour
= 0.04167 pulses/second
3
, the
93