Mitsubishi Electric GOT2000 Series Connection Manual page 100

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(For FUJI MICREX-SX SPH)
Item
Set this item when change the
Transmission
transmission speed used for
*1
communication with the connected
Speed
equipment. (Default: 38400bps)
Set this item when change the data
length used for communication with
*1
Data Bit
the connected equipment.
(Default: 8bits)
Specify the stop bit length for
*1
Stop Bit
communications. (Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
*1
Parity
during communication.
(Default: Even)
Set the number of retries to be
Retry
performed when a communication
error occurs. (Default: 3time)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Set this item to adjust the
transmission timing of the
Delay Time
communication request from the
GOT. (Default: 0ms)
*1
Leave the setting as default. If the set value is changed,
communication with the PLC is disabled.
POINT
POINT
POINT
(1) Host address
When connecting to PLC by RS-232
communication, set the Host Address to "0".
(2) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication Settings]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(3) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
4 - 16
4. CONNECTION TO FUJI PLC
4.2 Serial connection
Description
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
1 to 30sec
0 to 300ms